dc.description.abstractIn this study a new approach for the calculation of harmonic transformer parameters by making use of equivalent circuit model of one phase transformers is put forth. With this aim in mind, a three-phase core type transformer from 4 kVA, 400/230 V, 50 Hz, Yy0 connection group was used. To supply transformers voltage sources with sinusoidal and non-sinusoidal wave shapes were used. The transformers supplied on these sources were connected two different loads: one linear and one nonlinear. The interactions of these transformers, under different load and supplies, with harmonics were measured simultaneously with two harmonic analyzing devices connected to primer and secondary and the measurements up to the 15th harmonics were assessed and equivalent circuit components were calculated for each harmonic component separately. From the values measured and calculated, copper losses of primer and secondary circuits of three-phase transformers, iron losses and the efficiency of the transformer was calculated harmonically. Measurement and calculations were made separately for two different supplying and two different loads and results were compared. Besides, for each condition, total harmonic distortion (THD) of voltage and current and K factors were calculated, their effects on transformers performance were revealed. © 2011 Academic Journals.en_US
dc.identifier.doi10.5897/SRE11.829en_US
dc.identifier.endpage5522en_US
dc.identifier.issn1992-2248en_US
dc.identifier.issue26en_US
dc.identifier.scopusqualityN/Aen_US
dc.identifier.startpage5513en_US
dc.identifier.urihttps://dx.doi.org/10.5897/SRE11.829
dc.identifier.urihttps://hdl.handle.net/20.500.12395/27299
dc.identifier.volume6en_US
dc.indekslendigikaynakScopusen_US
dc.language.isoenen_US
dc.relation.ispartofScientific Research and Essaysen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.selcuk20240510_oaigen_US
dc.subjectEquivalent circuiten_US
dc.subjectHarmonicsen_US
dc.subjectK-factoren_US
dc.subjectLinear loadsen_US
dc.subjectNon-linear loaden_US
dc.subjectTransformer losesen_US
dc.titleThe effects of linear and non-linear loads on threephase transformers supplied from different sourcesen_US