Experimental study on ejector refrigeration system powered by low grade heat

dc.contributor.authorYapici, R.
dc.contributor.authorYetisen, C. C.
dc.date.accessioned2020-03-26T17:17:27Z
dc.date.available2020-03-26T17:17:27Z
dc.date.issued2007
dc.departmentSelçuk Üniversitesien_US
dc.description.abstractAn ejector refrigeration system has been designed and constructed to operate with hot water. Such a refrigeration system, designed for low pressure refrigerants, can be operated using energy sources such as solar energy, geothermal energy and waste heat. In this study, the effects of the main operating parameters on system performance were experimentally investigated using R-11 as the working fluid and keeping constant the position of the primary nozzle end at the inlet plane of the mixing chamber section of the ejector. The experimental study was performed over a range of vapor generator temperatures from about 90 to 102 C, evaporator temperatures from 0 to 16 C and condenser pressures from 114 to 143 kPa, and a COP up to 0.25 was obtained. It was seen that if higher cooling capacity and also lower evaporator temperature are desired from the system, the vapor generator temperature should be increased considerably. (C) 2006 Elsevier Ltd. All rights reserved.en_US
dc.identifier.doi10.1016/j.enconman.2006.11.015en_US
dc.identifier.endpage1568en_US
dc.identifier.issn0196-8904en_US
dc.identifier.issn1879-2227en_US
dc.identifier.issue5en_US
dc.identifier.scopusqualityQ1en_US
dc.identifier.startpage1560en_US
dc.identifier.urihttps://dx.doi.org/10.1016/j.enconman.2006.11.015
dc.identifier.urihttps://hdl.handle.net/20.500.12395/21400
dc.identifier.volume48en_US
dc.identifier.wosWOS:000245957800017en_US
dc.identifier.wosqualityQ1en_US
dc.indekslendigikaynakWeb of Scienceen_US
dc.indekslendigikaynakScopusen_US
dc.language.isoenen_US
dc.publisherPERGAMON-ELSEVIER SCIENCE LTDen_US
dc.relation.ispartofENERGY CONVERSION AND MANAGEMENTen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.selcuk20240510_oaigen_US
dc.subjectejectoren_US
dc.subjectrefrigerationen_US
dc.subjectcooling capacityen_US
dc.subjectoperating parametersen_US
dc.subjectlow grade heaten_US
dc.titleExperimental study on ejector refrigeration system powered by low grade heaten_US
dc.typeArticleen_US

Dosyalar