Preliminary experimental results on the R134a refrigeration system using a two-phase ejector as an expander

dc.contributor.authorErsoy, H. Kursad
dc.contributor.authorSag, Nagihan Bilir
dc.date.accessioned2020-03-26T18:58:25Z
dc.date.available2020-03-26T18:58:25Z
dc.date.issued2014
dc.departmentSelçuk Üniversitesien_US
dc.description.abstractThe use of an ejector as an expansion device instead of an expansion valve for expansion work recovery in a vapor-compression cycle was experimentally investigated. The coefficient of performance (COP) values for both conventional and ejector systems were experimentally investigated under the same external conditions. It was observed that, although the drop in the refrigerant pressure in the evaporator of the ejector system was almost negligible, it rose as high as 133 kPa in the conventional system. Depending on the operating conditions, it was found that the work recovery in the ejector was between 14% and 17%. It was also found that the refrigeration system with an ejector as the expander exhibited a COP that was 6.2-14.5% higher than that of the conventional system. The experimental results were found to comply with the theoretical results within an error of approximately 10%. (C) 2014 Elsevier Ltd and IIR. All rights reserved.en_US
dc.description.sponsorshipScientific and Technical Research Council of Turkey (TUBITAK)Turkiye Bilimsel ve Teknolojik Arastirma Kurumu (TUBITAK) [110M044]; Selcuk UniversitySelcuk University [13401071]en_US
dc.description.sponsorshipThis study was supported by the Scientific and Technical Research Council of Turkey (TUBITAK) under grant number 110M044. The authors also thanks to Prof. Dr. H. Selcuk Halkaci for his contribution as adviser of the project. In addition, the present paper constitutes a part of the ongoing PhD thesis of the second author, which is partially supported by the Selcuk University Scientific Research Project Coordinator (BAP Project No: 13401071).en_US
dc.identifier.doi10.1016/j.ijrefrig.2014.04.006en_US
dc.identifier.endpage110en_US
dc.identifier.issn0140-7007en_US
dc.identifier.issn1879-2081en_US
dc.identifier.scopusqualityQ1en_US
dc.identifier.startpage97en_US
dc.identifier.urihttps://dx.doi.org/10.1016/j.ijrefrig.2014.04.006
dc.identifier.urihttps://hdl.handle.net/20.500.12395/31080
dc.identifier.volume43en_US
dc.identifier.wosWOS:000340979900011en_US
dc.identifier.wosqualityQ1en_US
dc.indekslendigikaynakWeb of Scienceen_US
dc.indekslendigikaynakScopusen_US
dc.language.isoenen_US
dc.publisherELSEVIER SCI LTDen_US
dc.relation.ispartofINTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROIDen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.selcuk20240510_oaigen_US
dc.subjectRefrigerationen_US
dc.subjectEjectoren_US
dc.subjectThrottlingen_US
dc.subjectExpansionen_US
dc.subjectCOPen_US
dc.subjectR134aen_US
dc.titlePreliminary experimental results on the R134a refrigeration system using a two-phase ejector as an expanderen_US
dc.typeArticleen_US

Dosyalar